Save Investment
|
Advance Reliable Technology
|
Completed Protection
|
|
Simple Installation and
|
Items | FR-UK 3320 SPO-A | FR-UK 3330 SPO-A | FR-UK 3360 SPO-A |
DC Input |
|||
Battery Voltage (VDC) | 220/348/384 | ||
Charge Max. Current (A) | 40 | ||
Discharge Max. Current (A) | 68 | 106 | 176 |
Number of Input | 1 | ||
Ac Input |
|||
Voltage (VAC) | 380±20% (3F + N + G) |
||
Frequency (Hz) | 50/60 |
||
Current (A) | 84 | 108 | 150 |
Ac Ouput |
|||
Rated Power (KW) | 20 | 30 | 60 |
Voltage (VAC) | 380 (3F + N + G) (400/415 optional) |
||
Max. Output Current (A) | 28 | 46 | 76 |
Frequency (Hz) | 50/60 | ||
Max. Power Efficiency | >95% | ||
Wave Form | Pure sine wave, THD<3% at linear load | ||
Overload Capacity | 125% of rated load last for 10 min, 150% of rated load last for 1 sec |
||
Other | |||
Isolation Transformer | Internal (optional) |
||
AC/DC Switches | Internal | ||
LCD Display | LED indicator, LCD display input voltage, AC input voltage, output voltage, Load percentage (represent load current and inverter current),inverter frequency, energy today & accumulated energy (refer to SCC specification), etc. | ||
LED Display | Work status of inverter and fault indication | ||
Communication | Integrated Touch Screen Remote Monitoring Unit | ||
Protection | Output short circuit, Overload, Over Temperature, Battery low voltage, Output over/low Voltage, Reverse Polarity | ||
Protection Level | IP20 | ||
Noise (dB) | <65 | ||
Cooling | Fans | ||
Operating Temperature | -20°C~40°C | ||
Operating Altitude | <1000m without loss of power | ||
Relative Humidity | 0%~95% (no condensation) | ||
Dimensions (HxWxD) (mm) | 500 x 800 x 1180 | 800 x 800 x 1600 | |
Weight (kg) | 240 | 290 | 490 |
Marks | CE | ||
Directives | 2004/108/EC; 2006/95/EC |