Lower Investment, Higher Income
|
Highly Integrated
|
Advanced Intelligence
|
Efficient and Reliable
|
Items | SPI3125K-B-HUD/T | SPI6250K-B-HUD/T | SPI6800K-B-HUD/T |
DC Input | |||
Max. Input Voltage (Vdc) | 1500 Vdc | ||
Max. PV Input Current (A) | 3992 A | 2 x 3992 A | |
PV Input Strings Number | 16 ~ 24 optional | 2 x (16 ~ 24 optional) | |
No. of MPPTs | 2 (1 optional) | 2 x 2 (2 x 1 optional) | |
MPPT Voltage Range (Vdc) | 875 ~ 1500Vdc | ||
Start Up Voltage (Vdc) | 915 Vdc | ||
MPPT Efficiency | >99.90% | ||
AC Output | |||
Rated AC Output Power | 3125 kW | 2 x 3125 kW | 2 x 3400 kW |
Max. Output Power | 3438 kVA | 2 x 3438 kVA | 2 x 3438kVA |
Rated Grid Voltage | 10 ~ 35 kV | 20 ~ 35 kV | |
Rated Grid Frequency (Hz) | 50/60 | ||
Power Factor | >0.99 @rated power (-0.8 ~ +0.8 adjustable range) | ||
THDi | <3% (at rated power) | ||
Inverter Efficiency | |||
Max. Efficiency | 99.02% | ||
Euro Efficiency | 98.55% | ||
Transformer | |||
Transformer Type | Oil | ||
Rated Power | 3125 kVA | 6250 kVA | 6800 kVA |
Max Output Power | 3438 kVA | 6875 kVA | 6875 kVA |
Isolation mode | Dy11/Yd11 | Dy11y11/Yd11d11 | |
Protection | |||
Protection | LVRT function, Fault wave record diagnosis, Online upgrade, Night SVG function, Anti-PID function (optional), Transformer measuring and controlling device |
||
General Data | |||
Dimensions (W x H x D) | 5500 x 2650 x 2438 mm | 12192 x 2896 x 2438 mm | |
Weight | 13T | 26T | |
IP Grade | IP55 | ||
Transformer Cooling Type | ONAN | ||
Inverter Cooling Type | Intelligent forced air cooling | ||
Altitude | 3000m (standard)/ >3000m (optional) | ||
Operating Temperature Range | -35°C ~ +60°C | ||
Operating Humidity | 0 ~ 100% | ||
Display | LCD | ||
Communication | Ethernet, RS485 |