Highly Integrated
|
Efficient and Stable
|
Lean Intelligence
|
Flexible Configuration
|
Items | BCS2000K-B-HUD/T | BCS2500K-B-HUD/T | BCS3000K-B-HUD/T | BCS3450K-B-HUD/T |
DC Input | ||||
Max. DC Voltage (Vdc) | 1500 | |||
DC Voltage Range (Vdc) | 700~1500 | 800~1500 | 900~1500 | 1000~1500 |
Max DC Current (A) | 3206 | 3508 | 3742 | 3872 |
Auto Buering Function | Yes | |||
Grid-tied AC Output | ||||
Rated AC Output Power (kW) | 2000 | 2500 | 3000 | 3450 |
Max. AC Output Power (kVA) | 2200 | 2750 | 3300 | 3795 |
Rated Output Voltage (Vac) | 440 | 550 | 600 | 690 |
Output Voltage Range | -15% ~ 10% (settable) | |||
Rated Grid Frequency (Hz) | 50/60 (settable) | |||
Max Output Current (A) | 2886 | 2886 | 3176 | 3176 |
Adjustable Power Factor | >0.99 (at rated power)/1 (leading) ~ 1 (lagging) | |||
THDi | <3% (at rated power) | |||
Off-Grid AC Output | ||||
Rated AC Output Voltage (Vac) | 440 | 550 | 600 | 690 |
Max. Output Current (A) | 2886 | 2886 | 3176 | 3176 |
THDu | <3% (linear load) | |||
Rated Output Frequency (Hz) | 50/60 | |||
Overloading Capability | 110% overload | |||
Efficiency | ||||
Max. Efficiency | 99.03% | |||
Transformer Efficiency | ||||
Rated Power (kVA) | 2000 | 2500 | 3000 | 3450 |
Voltage transformation Ratio | 0.44/(6~35)kV | 0.55/(6~35)kV | 0.6/(6~35)kV | 0.69/(6~35)kV |
Isolation Mode | oil-immersed transformer or dry type transformer | |||
General Data | ||||
IP Grade | IP55 | |||
Operation Temperature | -30 ~ 65°C (>50°C derating) | |||
Relative Humidity | 0 ~ 100% (no condentation) | |||
Cooling Type | Intelligent forced air cooling | |||
Dimensions (W x H xD)(mm) | 5670 x 2525 x 2462 | |||
Weight (kg) | 13000 | |||
Altitude (m) | 4000 m (>2000 m derating) | |||
Display | Touch screen | |||
Communication Protocol | Modbus-RTU/Modbus-TCP/IEC61850/IEC104 | |||
Communication Interface | RS485/ Ethernet | |||
Standard | GB/T 34120, IEC62477, EN61000, EN62116 |